Design and model: Intelligent solid-state current limiter to prevent sympathetic tripping problem on power and energy applications

Date

2019-08

Journal Title

Journal ISSN

Volume Title

Publisher

Abstract

This paper analyzes the Sympathetic Tripping Problem and proposes and tests a solution to it. To do so, it considers a case study, develops a model to explain this case study, and uses this model to test X. The results reveal that transferring power near the system voltage stability limit is a major cause of the Sympathetic Tripping Problem. Limiting fault current and using synchronous condensers for reactive power support were shown to solve the Sympathetic Tripping Problem.

Description

Rights

Availability

Restricted until 2021-09.

Keywords

Sympathetic tripping, Voltage dip, Air conditioner stalling, Fault current limiting

Citation